Water hardness: what it is and how it is measured

Hardness is dissolved calcium and magnesium — the minerals behind scale in geysers, kettles and membranes. The units are the confusing part; the chemistry is simple.

Written by the Definitive Water Technologies team · Technically reviewed by Chandré Naudé, BEng (Civil) · Published

The chemistry in one paragraph

Hardness is the sum of dissolved calcium (Ca²⁺) and magnesium (Mg²⁺) in water. Rain picks these up as it percolates through limestone and dolomite, which is why borehole water in dolomitic areas is hard while water off sandstone catchments (like much of the Western Cape) is soft. The ions themselves are harmless to drink — hardness is an equipment problem, not a health problem.

Why it matters to equipment

When hard water is heated or concentrated, calcium carbonate comes out of solution as scale. Scale insulates heating elements (a few millimetres can add double-digit percentages to heating energy), narrows pipes, blinds RO membranes, and coats UV quartz sleeves. Hardness also reacts with soap to form scum, which is why laundries and car washes care about it long before scaling appears.

The units — where everyone gets caught

All hardness units express the same thing; they just use different yardsticks.

UnitMeaning1 unit equals
mg/L as CaCO₃The SA and international lab standard1 ppm CaCO₃
German degrees (°dH)Common on European equipment17.85 mg/L CaCO₃
French degrees (°f)Common on softener datasheets10 mg/L CaCO₃
Grains per gallon (gpg)US softener capacity ratings17.1 mg/L CaCO₃

The trap: a lab report might state calcium as mg/L Ca, not mg/L as CaCO₃. Multiply mg/L Ca by 2.5 (and mg/L Mg by 4.1) to convert to the CaCO₃ basis before comparing against any datasheet.

Classifying a water

mg/L as CaCO₃Classification
0 – 60Soft
61 – 120Moderately hard
121 – 180Hard
> 180Very hard

As a working trigger: geysers, boilers and steam equipment start complaining above roughly 120 mg/L; RO systems need scale control (softening or antiscalant) evaluated at almost any hardness once recovery is pushed, because the concentrate stream is several times more concentrated than the feed.

Temporary versus permanent

Temporary hardness (carbonate hardness) is the fraction paired with bicarbonate alkalinity — it is the part that precipitates when water is boiled. Permanent hardness is paired with chloride and sulphate and stays in solution through boiling. The distinction matters mainly for chemistry calculations; a softener removes both, because ion exchange does not care which anion the calcium arrived with.

Rule of thumb: get everything onto mg/L as CaCO₃ before you compare numbers, and treat 120 mg/L as the point where heated equipment starts paying for hardness. What to do about it — softening, anti-scale cartridges or antiscalant dosing — is covered in the softening section.

Specifying for a real project? Send the duty details and the branch will confirm the right selection.

Request a quote

General engineering guidance reviewed by DWT’s technical team. It does not replace manufacturer datasheets or a site-specific design; confirm selections against the actual water analysis and duty conditions.