Runxin valve codes — new numbering explained and converted

Decode Runxin's new five-digit valve codes position by position, convert old F-series codes (F67C1) to new numbers and back, and build a code from application, control type and flow rate.

1. The ranges DWT keeps on the shelf

These are the Runxin ranges DWT and most South African distributors stock — the industry-standard set for their flow classes. Spec one of these unless the duty genuinely demands otherwise: everything else in the catalogue is imported on order with a longer lead time.

F67 — 1" automatic filter valve

DWT stocked
Connections
1" F
Rated flow
4 m3/h (6 m3/h -A riser)
Duty
Filter — F63 is the softener twin
Common codes
53504 (F67C1, time) / 53604 (F67C3, meter)

Inlet LEFT — flow left to right

Facing the display, the inlet is on the LEFT — flow runs left to right. (Manual drawings; the meter probe wire runs to the right-hand outlet port.)

F63 — 1" automatic softener valve (downflow)

DWT stocked
Connections
1" M
Rated flow
4 m3/h
Duty
Softener — F67 is the filter twin
Common codes
63504 (F63C1, time) / 63604 (F63C3, meter)

Inlet LEFT — flow left to right

Facing the display, the inlet is on the LEFT — flow runs left to right. Same body platform as the F67 filter. NOTE: the newer F116 that Runxin positions as the F63 upgrade is piped the OPPOSITE way.

F75 / N75 — 2" automatic filter valve

DWT stocked
Connections
2" M
Rated flow
10 m3/h
Duty
Filter — F74 / N74 is the softener twin
Common codes
53510 (N75A1, time) / 53610 (N75A3, meter)

Inlet RIGHT — flow right to left

Facing the display, the inlet is on the RIGHT — flow runs right to left. This is where the direction flips from the smaller 1" valves.

F74 / N74 — 2" automatic softener valve

DWT stocked
Connections
2" M
Rated flow
10 m3/h
Duty
Softener — F75 / N75 is the filter twin
Common codes
63510 (F74A1, time) / 63610 (F74A3, meter)

Inlet RIGHT — flow right to left

Facing the display, the inlet is on the RIGHT — flow runs right to left. (Manual structure chart read against Runxin's own rear product photo; the flow meter sits on the left-hand outlet.)

F77 — 2" automatic valve, side- or top-mounted

DWT stocked
Connections
2" M
Rated flow
18 m3/h
Duty
Softener (F77A) / filter (F77B)
Common codes
63518 (F77A1) / 63618 (F77A3) / 53518 (F77B1, time only)

Inlet RIGHT — flow right to left

Facing the display, the inlet is on the RIGHT — flow runs right to left. (Dimension drawing, flow-meter figure and the pressure-gauge-on-inlet figure all agree.)

F112 — DN65 side-mounted automatic valve

DWT stocked
Connections
DN65 flanged
Rated flow
40 m3/h
Duty
Softener (F112A) / filter (F112B)
Common codes
63540B (F112A1) / 63640B (F112A3) / 53540B (F112B1)

Inlet LEFT — flow left to right

Facing the display, the inlet is on the LEFT — flow runs left to right (pressure gauge on the left inlet, flow meter on the right outlet in Runxin's own drawings and install photo). Note this is OPPOSITE to the 2" F74/F75/F77 family.

2. How the new code works

New-style Runxin codes pack the specification into five digits: product family, platform, regeneration start, and rated flow. Type any code to decode it position by position.

6

Softener — downflow regeneration

3

Standard automatic (LED)

6

Volume (meter) start

02

Flow designation 2 in the code — confirm the model's actual rated service and backwash flows against the manufacturer's data before selecting

63602 corresponds to the old code F65B3.

F65 valves are available on order — longer lead time, and typically not readily stocked by South African distributors. Ask the branch whether a stocked range covers the duty. Facing the display, the inlet is on the LEFT — flow runs left to right. NOTE: the newer F130 replacement is piped the OPPOSITE way.

3. Convert between old and new codes

Enter either format — an old F- or N-series code (F67C1, N75A1) or a new numeric code (53504) — and get its counterpart from the official pairing.

F67C1 is now 53504.

F67 is a range DWT keeps on the shelf. Facing the display, the inlet is on the LEFT — flow runs left to right. (Manual drawings; the meter probe wire runs to the right-hand outlet port.)

4. Build a code from your requirement

Pick what the duty needs; the convention gives the new code, and the table shows the old code where one exists.

63602

In the table: old code F65B3.

F65 valves are available on order — longer lead time, and typically not readily stocked by South African distributors. Ask the branch whether a stocked range covers the duty. Facing the display, the inlet is on the LEFT — flow runs left to right. NOTE: the newer F130 replacement is piped the OPPOSITE way.

5. Which side is the inlet?

Runxin ranges do NOT all pipe the same way round, and plants have been laid out backwards because of it. Directions below are stated facing the controller display and were verified against Runxin’s own manuals and drawings. Before fabrication, always confirm against the moulded IN/OUT arrows on the valve body itself.

RangeDirection
F671" F · 4 m3/h (6 m3/h -A riser)DWT stockedInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right. (Manual drawings; the meter probe wire runs to the right-hand outlet port.)
F631" M · 4 m3/hDWT stockedInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right. Same body platform as the F67 filter. NOTE: the newer F116 that Runxin positions as the F63 upgrade is piped the OPPOSITE way.
F752" M · 10 m3/hDWT stockedInlet RIGHT — flow right to leftFacing the display, the inlet is on the RIGHT — flow runs right to left. This is where the direction flips from the smaller 1" valves.
F742" M · 10 m3/hDWT stockedInlet RIGHT — flow right to leftFacing the display, the inlet is on the RIGHT — flow runs right to left. (Manual structure chart read against Runxin's own rear product photo; the flow meter sits on the left-hand outlet.)
F772" M · 18 m3/hDWT stockedInlet RIGHT — flow right to leftFacing the display, the inlet is on the RIGHT — flow runs right to left. (Dimension drawing, flow-meter figure and the pressure-gauge-on-inlet figure all agree.)
F112DN65 flanged · 40 m3/hDWT stockedInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right (pressure gauge on the left inlet, flow meter on the right outlet in Runxin's own drawings and install photo). Note this is OPPOSITE to the 2" F74/F75/F77 family.
F713/4" M · 2 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right.
F653/4" F · 2 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right. NOTE: the newer F130 replacement is piped the OPPOSITE way.
F693/4" F · 2 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right.
F681" M · 4 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right.
F1341.5" M · 8 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right (the body is embossed OUT with an arrow on the right of the display face).
F1331.5" M · 8 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right (the body is embossed OUT with an arrow on the right of the display face).
F992" M · 15 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT — flow runs left to right. Careful: unlike the other 2" valves (F74/F75/F77), the F99 runs left to right — all three of its manual drawings agree.
F96DN80 · 40-50 m3/hInlet LEFT — flow left to rightFacing the display, the inlet is on the LEFT and the outlet lower-right — flow runs left to right (labelled structure drawings with the display visible).
F1161" M · 4-6 m3/hInlet RIGHT — flow right to leftFacing the display, the inlet is on the RIGHT — flow runs right to left. TRAP: this is the OPPOSITE of the F63 it replaces (verified from the embossed IN/OUT on the body in the manual's rear views and the catalogue photo).
F1173/4" F · 2-3 m3/hInlet RIGHT — flow right to leftFacing the display, the inlet is on the RIGHT — flow runs right to left. TRAP: this is the OPPOSITE of the F65 it replaces (the IN embossing is visible on the right of the manual's display-facing view).
F1301" M · 5 m3/hInlet RIGHT — flow right to leftFacing the display, the inlet is on the RIGHT — flow runs right to left. TRAP: opposite to the F65/F69 generation they update (embossed IN/OUT in the manual's rear views).
F1112" M · 20 m3/hDiffers by modelTop-mounted with a movable screen, so left/right depends on how the head is oriented — pipe to the moulded IN/OUT arrows on the valve body, not to the screen.
F952" M · 20 m3/hVertical connectionsService connections are VERTICAL (top/bottom distributor pipework on a seat frame) and the top/bottom assignment differs between models — e.g. Runxin draws the 93620 with outlet top and the 63620 with inlet top. Work from the model's own structure drawing.
F147DN65 · 30 m3/hVertical connectionsService connections are VERTICAL: inlet bottom, outlet top (moulded IN/OUT arrows on the body per the manual's structure drawing).
F793/4" M (F79) / 1" M (F82) · 2-3.5 m3/hBoth ports on one sideInlet and outlet are stacked on ONE side of the valve (bypass-style quick connections): the outlet is the UPPER port — the flow meter sits on it — and the inlet the lower.
F731" M · 3.5 m3/hBoth ports on one sideBoth service ports face down under the valve body: the outlet is the port the flow meter screws into, the inlet the one beside it — check the meter position before piping.
F881.5" M (F88) / 1" M (F98) · 6-10 m3/hDiffers by modelRunxin's manual states the SAME hardware becomes either code by which way you point the outlet: outlet to the left = 93610/93606, outlet to the right = 17610/17606. Decide the direction on the drawing before ordering.
F1181" (connectors a/b) · 4 m3/hDiffers by modelThe two G1 connectors SWAP roles between models: on F118A/F118AR connector a is the inlet; on F118B/F118BR connector a is the outlet (raw-water vs soft-water regeneration — Runxin's own table). Confirm the model before piping.
F77S2" M · 15 m3/hDiffers by modelHandwheel valves with no display to orient by — work from the port labels on the structure drawing in the F77AS/BS manual, and note the side-mounted F77CS is installed with the connector upside down.
F561/2"-2" (by model) · 1-10 m3/hDiffers by modelPort positions differ by model — see the labels on each drawing in the F56 leaflet. Runxin's own note warns the F56F is piped OPPOSITE to the printed diagram.

Ranges not listed here have no orientation stated in Runxin’s published documents — send the code with a quote request and the branch will confirm from the drawing before you commit a layout.

6. Full cross-reference table

The complete Runxin range beyond the stocked set is available on order — expect a longer lead time, as these models are typically not readily stocked by South African distributors.

Reference compiled from the official Runxin product catalogue, the code lists and structure drawings in Runxin’s per-series instruction manuals, and run-xin.com product pages. Runxin’s own documents occasionally print two codes for one valve — the notes column flags every case we found. Runxin is a trademark of its owner; DWT stocks and sources Runxin valves. Always confirm the exact model against the Runxin datasheet before ordering — variants (suffix letters, port sizes, riser sizes) matter in service.